Concrete Foundation



"Concrete Foundation Sample Plan" located at bottom of this page.


General Notes:
Use fill with P. I. ( Plasticity Index) not to exceed 20: except where water table is encountered, use gravel, crushed stone or comparable material.

Exterior and interior beams shall be a minimum depth below natural grade of 6”. (Exception: when the exterior beams are placed on a compacted fill of 90% standard proctor density beams shall not be required to extend below natural grade, but shall be required to extend below finished grade a minimum of 6” into the compacted fill.) Exterior beams shall have a minimum of 9" of cover from the bottom of the beam. (See Detail A)

All concrete shall be of a design mix to have a 28-day compressive strength of 3,000 psi.

Dead end beams not allowed except for corner support beams. Corner support beams shall pass through one intersecting beam and may dead end after connecting with the next intersecting beam. (See Detail on Concrete Foundation Sample Plan)

All beam and slab reinforcing shall maintain minimum clearance of 2” from exterior forms on sides.
All beam and slab reinforcing shall maintain minimum clearance of 3" from bottom of beam.

Beam reinforcing shall be tied and supported every 4’-0” minimum.

Top corner reinforcing steel (bars) required at all perimeter beams. (See Typical Corner Bar Detail)

LAP splices shall be in accordance with the following:


A Foundation Plan will be required for all construction.